Cleaned for industrial oxygen service Dual Seal approval (FM*Only available for Range options 04 thru 08 **For pressure Ranges above 0-10,000 psi (Range options 10 and 11) ***Dual Seal version is not hermetically sealed. Only available for Range options 00 thru 09Note: The continuous zero and span points and the Switch Conffguration Mode and set point(s) must be speciffed. Refer to switch conffguration diagrams on page 3.Example: 815PT-Z07-A-RR, which has a range of 0-2500 psi could be ordered with zero and span of 200 psi and 2300 psi. The window mode switch conffguration could have a LO set point of 210 psi and a HI set point of 2290 psi. )*** Pipe mounting kit SS tag wired to housing with customer speciffed information815PT Smart Pressure Transmitter, HART 7 Communication Protocol with 4-20 mA Output, Modbus RTU (RS-485) Serial Communications, 1-5 VDC (Low-Power) Mode of Operation, Conffgurable Solid-State Switch Output, 0-2500 psi, 17-4SS Port, ½” NPT(M) with ¼” NPT(F) Process Connection, an. This diagram depicts an adjustable dead band. Dead band is the range through which an input can be varied without initiating an observable response. Dead band is usually expressed in percent of span. EXAMPLE: A 20% total dead band is In this conffguration, the switch output will be closed for pressures less than the selected setpoint. The switch output would then be open for pressures greater than the setpoint. applied to the setpointd Optional SS Tag Wired to Housing with Customer Speciffed Information.